BY1-12.5-XXX/1(S) 75 150 275 320 385 440 | ||||||||
Listrik IEC | ||||||||
Tegangan AC Nominal (50/60Hz) | U₀/Un | Tegangan 60V | Tegangan 120V | Tegangan 230V | Tegangan 230V | Tegangan 230V | Tegangan 400V | |
Tegangan Operasi Kontinu Maksimum (AC) | Ue | tegangan 75V | Tegangan 150V | Tegangan 275V | Tegangan 320V | 385V | Tegangan 440V | |
Arus Pelepasan Nominal (8/20μs) | In | 20kA | 20kA | 20kA | 20kA | 10kA | 10kA | |
Arus Pelepasan Maksimum (8/20μs) | maksimal | 50kA | 50kA | 50kA | 50kA | 50kA | 50kA | |
Arus Pelepasan Impuls (10/350μs) | lemas | 12,5kA | 12,5kA | 12,5kA | 12,5kA | 10kA | 10kA | |
Energi Spesifik | W/R | 39kJ/Q | 39kJ/Ω | 39kJ/Ω | 39kJ/Ω | 25kJ/Ω | 25kJ/Ω | |
Mengenakan biaya | Q | 6.25As | 6.25As | 6.25As | 6.25As | 5A | 5A | |
Tingkat Perlindungan Tegangan | Up | Tegangan 700V | Tegangan 1000V | Tegangan 1500V | Tegangan 1600V | Tegangan 1800V | 2000V | |
Waktu Respon | tA | <25 detik | ||||||
Sekring Cadangan (maks) | 315A/250AgG | |||||||
Nilai Arus Hubung Singkat (AC) | lscCR | Tegangan 25kA/50kA | ||||||
TOV Tahan 5 detik | UT | 114V | 180 | 335V | 335V | 335V | Tegangan 580V | |
UT | Tegangan 180V | Tegangan 230V | Tegangan 440V | Tegangan 440V | Tegangan 440V | 765V | ||
TOV 120 menit | Mode | Menahan | Gagal Aman | Gagal Aman | Gagal Aman | Gagal Aman | Gagal Aman | |
Jumlah Pelabuhan | 1 | |||||||
ULElektrikal | ||||||||
Tegangan Operasi Kontinu Maksimum (AC) | Bahasa Indonesia: MCOV | tegangan 75V | Tegangan 150V | Tegangan 275V | Tegangan 320V | 385V | Tegangan 440V | |
Peringkat Perlindungan Tegangan | VPR | Tegangan 330V | Tegangan 600V | Tegangan 900V | Tegangan 1200V | Tegangan 1350V | Tegangan 1500V | |
Arus Pelepasan Nominal (8/20 μs) | SAYA. | 20kA | 20kA | 20kA | 20kA | 20kA | 20kA | |
Nilai Arus Hubung Singkat (AC) | skr | 100kA | 200kA | 150kA | 150kA | 150kA | 200kA | |
Mekanik & Lingkungan | ||||||||
Kisaran Suhu Operasional Ta | -40F hingga +158F[-40℃ hingga +70℃] | |||||||
Kelembaban Operasional yang Diizinkan RH | 5%…95% | |||||||
Tekanan atmosfer dan ketinggian | 80 ribu Pa…106 ribu Pa/-500 m..2000 m | |||||||
Torsi Sekrup Terminal Mmax | 39,9 Ibf · dalam [4,5 Nm] | |||||||
Penampang Konduktor (maks) | 2AWG (Padat, Terdampar)/4 AWG (Fleksibel) 35mm² (Padat, Terdampar)/25mm² (Fleksibel) | |||||||
Pemasangan | Rel DIN 35mm, EN 60715 | |||||||
Tingkat Perlindungan | IP20 (bawaan) | |||||||
Bahan Perumahan | Termoplastik: Tingkat Pemadaman UL94 V-0 | |||||||
Perlindungan Termal | Ya | |||||||
Status Pengoperasian/Indikasi Kesalahan | Hijau ok/Cacat merah | |||||||
Kontak Jarak Jauh (RC) | Opsional | |||||||
Kapasitas Pengalihan RC | AC:250V/0,5A;DC:250V/0,1A;125V/0,2A;75V/0,5A | |||||||
Penampang Konduktor RC (maks) | 16AWG (Padat)/1,5mm² (Padat) |