IEC Listrik
| Tegangan AC Nominal (50/60Hz) | 120V | 230V | 230V | ||
| Tegangan Operasi Kontinu Maksimum (AC) | (LN) | Uc | 150V | 275V | 320V |
| (N-PE) | Uc | 255V | 255V | 255V | |
| Arus Pelepasan Nominal (8/20)μs) | (LN)/(N-PE) | In | 20 kA/25 KA | ||
| Arus Pelepasan Maksimum (8/20)μs) | (LN)/(N-PE) | lmaksimal | 50kA/100KA | ||
| Arus Pelepasan Impuls (10/350)μs) | (LN)/(N-PE) | limp | 12,5 kA/50KA | ||
| Energi Spesifik | (LN)/(N-PE) | W/R | 39kJ/Ω/625KJ/Ω | ||
| Mengenakan biaya | (LN)/(N-PE) | Q | 6A/12,5A | ||
| Tingkat Perlindungan Tegangan | (LN)/(N-PE) | Up | 1000V/1500V 1500 V/1500V 1600V/1500V/ | ||
| Ikuti Peringkat Interupsi Saat Ini | (N-PE) | I | 100ARMS | ||
| Waktu Respons | (LN)/(N-PE) | tA | <25 ns/<100ns | ||
| Sekring Cadangan (maks) | 315A/250A gG | ||||
| Peringkat Arus Hubung Singkat (AC) | (LN) | lscCR | 25 kA/50 kA | ||
| Ketahanan TOV 5 detik | (LN) | UT | 180V | 335V | 335V |
| TOV 120 menit | (LN) | UT | 230V | 440V | 440V |
| Mode | Kegagalan Aman | Kegagalan Aman | Kegagalan Aman | ||
| TOV Tahan 200 detik | (N-PE) | UT | 1200V | ||
| Jumlah Pelabuhan | 1 | ||||
UL Listrik
| Tegangan Operasi Kontinu Maksimum (AC) | (LN)/(N-PE) | MCOV | Tegangan 150V/255V | 275V/255V | 320V/255V |
| Peringkat Perlindungan Tegangan | (LN)/(N-PE) | Wakil Presiden | 600V/1200V | 900V/1200V | 1200V/1200V |
| Arus Pelepasan Nominal (8/20μs) | (LN)/(-PE) | In | 20KA/20KA | 20KA/20KA | 20KA/20KA |
| Peringkat Arus Hubung Singkat (AC) | (LN) | SCCR | 150KA | 150KA | 150KA |
Mekanikal & Lingkungan
| Kisaran Suhu Operasional | Ta | -40 F hingga +158F[-40℃hingga +70℃I |
| Kelembaban Operasi yang Diizinkan | RH | 5%…95% |
| Tekanan atmosfer dan ketinggian | 80k Pa...106k Pa/-500m...2000m | |
| Torsi Sekrup Terminal | Mmax | 39,9 lbf-in [4,5 Nm] |
| Penampang Konduktor (maks) | 2AWG (Padat, Beruntai)/4AWG (Fleksibel) | |
| 35 mm²(Padat, Beruntai)/25 mm²(Fleksibel) | ||
| Pemasangan | Rel DIN 35 mm. EN 60715 | |
| Tingkat Perlindungan | IP 20 (terintegrasi) | |
| Bahan Perumahan | Termoplastik: Tingkat Pemadaman UL94V-0 | |
| Perlindungan Termal | Ya | |
| Status Operasi/Indikasi Kerusakan | Hijau oke/Merah cacat | |
| Kontak Jarak Jauh (RC) | Opsional | |
| Kapasitas Pengalihan RC | AC:250V/0.5A ABC:250V/0.1A A:125V/0.2A;75V/0.5A | |
| Penampang Konduktor RC (maks) | 16AWG (Padat)/1,5mm²(Terjual) |
Informasi Pemesanan
| Memesan Kode | 150 | 275 | 320 |
| BY1-12.5-XXX/3+1 | 1215033 | 1227533 | 1232033 |
| BY1-12.5-XXX/3S+1(dengankontak jarak jauh) | 1215034 | 1227534 | 1232034 |
| BY1-12.5-XXX/0 (modul cadangan) | 1215001 | 1227501 | 1232001 |
| BY1-12.5-NPE/0 (modul cadangan) | 1255002 | 1225502 | 1225502 |
Legenda
Jalur L
N Netral
PE Pelindung Tanah
Kontak Sinyal S Opsional
| BY1-12.5-XXX/3(S)+1 | 150 | 275 | 320 |
| Dimensi Unit Tunggal DIN 43880 | 1 CTN | ||
| Dimensi Kemasan (T×L×P) | [200×230×330 mm] | ||
| Jumlah Pesanan Minimum | 16Satuan | ||
| BY1-12.5-XXX/0 | 150 | 275 | 320 |
| BY1-12.5-NPE/0 | 50 | ||
| Dimensi Unit Tunggal DIN 43880 | 1 CTN | ||
| Dimensi Kemasan (T×L×P) | [200×230×330 mm] | ||
| Jumlah Pesanan Minimum | 64Satuan | ||